Submittal

Job __________________________
Designer ______________________
Contact _______________________
www.tekmarcontrols.com  of 2 © 20 C 334 - 0/




0/
Zoning
Replaces: New

The tekmarNet
®
2 Zone Manager 334 is designed to provide a zoning solution for 2-wire tekmarNet
®
2 thermostats used in heating
systems. It can be used in applications ranging from baseboard zones, to remote manifolds for radiant heating. This control energizes
up to 4 zone valves or zone pumps. It is capable of providing power for up to 4 tekmarNet
®
2 thermostats and energizing their respective
24 V (ac) or 5 V (ac) zones, as well as providing a powered Zone Group Pump (powered end switch) contact to enable an external
device such as a manifold pump.

This control is designed for use ONLY with tekmarNet
®
2 Thermostats.

--------------------------
Only requires 2 wires per zone
For use with tekmarNet
®
2 thermostats
ONLY
tekmarNet
®
2 compatible
Four zone valves or zone pumps
Time delay for thermal motor zone valves
CSA C US Certified for use in USA and
Canada
Provides power to tekmarNet
®
4 reset
module

-----------------------------------------------------
Front View
8–1/16”
(204 mm)
11–1/8”
(282 mm)
8–1/16”
(204 mm)
2–7/8
(74 mm)
7/16” (11 mm)
CL
7/16”
(11 mm)
3/16”
(5 mm)
Input Power
16 17
NL
Zn Grp
18
Pump C / N
Zone Power
19 20
R / L C / N
Zone 1
21 22
Vlv/Pmp C / N
Zone 2
23 24
Vlv/Pmp C / N
Zone 3
25 26
Vlv/Pmp C / N
Zone 4
27 28
Vlv/Pmp

tektra 1029-01
For product instructions, see brochure
Input Power: 115 V (ac) ±10% 60 Hz, 12 A
Relay Rating: 115 V (ac) 5 A
All Loads Using Input Power: 11.7 A
Zone Power: 115 V (ac) ±10% 60 Hz, 12 A
For product literature:
www.tekmarcontrols.com
Power Zone 1
Zone 2
Zone 3
Zone 4
tN4
Zone Group Pump
Cooling
Fan
Meets Class B:
Canadian ICES
FCC Part 15
Made in
Canada
Caution! Disconnect All
Power before Opening
24 V (ac) Fuse: T1.25 A 250 V
On/Off
H7017A
Zone Group
Pump Delay
Zone Group
Pump
GYRc
13 1514
tN2
Zone 3
tN2
Zone 2
tN2
Zone 1
tN2 tN2tN2Pmp
4
tN4 C
1 2 3
tN4 Expansion
5 VA Max
1
2
3
4
1
2
3
4
R
107 8 9
tN2
Zone 4
tN2
1211
Zn 4 Cool Fan
5 6
Cool & Fan Relay Rating:
24 V (ac) 2 A
Supply wires
75°C minimum
tN2
Four Zones, Cooling & Fan
Literature D334, W334, J334
Control Microprocessor control. This is not a safety (limit) control
Packaged weight 4.9 lb. (2220 g)
Dimensions 3-5/8” H x 5-3/8” W x 9/6” D (92 x 37 x 4 mm)
Enclosure
Blue PC+ABS plastic with metal top and bottom
conduit
connection walls, NEMA type 
Approvals CSA C US, meets Class B: ICES & FCC Part 5
Ambient conditions
Indoor use only, 32 to 09°F (0 to 43°C), RH ≤80% to 88°F
(3°C), down to 50% above 04°F (40°C), Altitude <6560 ft.
(2000 m), Installation Category II, Pollution Degree 2
Input power supply 5 V (ac) +/- 0%, 60 Hz, 2 A max
Combined load All loads using input power .7A max
Zone power 5 V (ac) +/- 0%, 60 Hz, 2 A max
Zone group pump
relay
5 V (ac) 5 A
Zone relays 5 V (ac) 5 A
Transformer power
available
24 V (ac) 7 VA, fuse T.25 A 250 V
Cool and fan relays 24 V (ac) 2 A
Warranty Limited 3 Year (See D334 for full warranty)
Side View
1/2” Knock-out
(x 16 back) (x 8 top)
(x 8 bottom) (x 2 side)

Summary of content (2 pages)