Wiring Brochure

3 of 12 © 2008 W 325 - 12/08
Electrical Drawings
Module Installation
The electrical drawing examples on the following
pages show the 325 in common applications. Choose
the drawing that most accurately depicts the components
in your system and use that drawing as a guide to aid in
wiring your system.
These are only concept drawings, not engineered drawings.
They are not intended to describe a complete system nor
any particular system. It is up to the system designer to
determine the necessary components for and configuration
of the particular system being designed including additional
equipment isolation relays (for loads greater than the
controls specified output ratings) and any safety devices
which in the judgement of the designer are appropriate in
order to properly size, configure and design that system
and to ensure compliance with building and safety code
requirements.
Install the Zone Expansion Module 325 in the left side of a tekmarNet
®
4 (tN4) wiring enclosure. The enclosure comes with
a Zone Manager pre-installed in the right side. Review the figure below to understand the installation of the 325:
To Install the 325
1. Remove the front cover of the wiring enclosure by
removing the two screws.
2. Remove the left side blank by removing the center screw
holding the blank and the Zone Manager in place. Make
sure the Zone Manager stays in place.
3. Discard the blank.
4. The 325 has connector pins protruding from the
underside of the board. The Zone Manager has two
wiring harnesses with plugs. Remove the larger gauge
wiring harness from its retaining clip in the enclosure.
The smaller one is not required.
5. Carefully connect the Zone Manager’s free plug onto
the pins on the underside of the 325.
Take care to ensure a good connection and avoid
bending the pins.
6. Lower the 325 into the enclosure at an angle. Insert the
two tabs on the left side of the 325 in to the corresponding
slots in the left side of the wiring enclosure.
7. Lower the 325 toward the center of the enclosure until
the two halves fit together. Make sure that the connector
wires are placed underneath without pinching the wire.
8. Replace the center screw to hold the two controls in
place.
9. Strip all wiring to a length of 3/8 in. or 10 mm for all
terminals.