Testing the Zone Group Pump C Output Terminals 89, 90
1. Remove the front cover from the control.
2. Use an electrical test meter to measure the (ac) voltage
between the Zone Group Pump C terminals (89, 90).
When the Zone Group Pump C light is off, the reading
should be 0 V (ac) and the pump should be off.
When the Zone Group Pump C light is on, the reading
should be 115 V (ac) + / – 10% and the pump should be
running.
Note: If the pump does not operate properly, refer to
any troubleshooting information supplied by the pump
manufacturer.
Testing the Zone Valve Outputs Terminals 77-88
1. Remove the front cover from the control.
2. Use an electrical test meter to measure the (ac) voltage
between the C and the Vlv terminals for each zone valve
output.
When the Zone light is off, the reading should be 0 V (ac)
and the valve should be closed.
When the Zone light is on, the reading should be
24 V (ac) + / – 10% and the valve should be open.
3. If power is not present:
Check the power supply to the Zone Manager and the
field replaceable fuse for the transformer on the Zone
Expansion Module.
If the power light is amber instead of green the transformer
fuse is blown. Determine the cause of the failure before
replacing the fuse.
Note: If the zone valve does not operate properly, refer
to any troubleshooting information supplied by the zone
valve manufacturer.