Submittal Sheet

Job __________________________
Designer ______________________
Contact _______________________
www.tekmarcontrols.com  of 2 © 20 C 35 - 0/




0/
Zoning
Replaces: New

5–1/2
(140 mm)
5–1/2
(140 mm)
1–1/8” (30 mm)
7/8
(22 mm)
CL
The tekmarNet
®
4 Wiring Center 35 is designed to provide a zoning solution for heating systems. It can be used in applications ranging
from baseboard zones, to remote manifolds for radiant heating. This control energizes up to 6 zone valves. It is capable of providing
power for up to 6 tekmarNet
®
4, or stand alone thermostats, and energizing their respective 24 V (ac) zones, as well as providing an
end switch closure to enable an external device such as a boiler.

Designed for use with tekmarNet
®
4 Thermostats.

--------------------------
Six 24 V (ac) powered zone outputs
For use with tekmarNet
®
4 thermostats
tN4 expansion terminals
Isolated end switch
External diagnostic LEDs
CSA C US Certified for use in USA and
Canada

-----------------------------------------------------
Six Zone Valves
Literature D35, Q35
Control Microprocessor control. This is not a safety (limit) control
Packaged weight .4 lb. (630 g)
Dimensions 5.5” H x 5.5” W x 2.25” D (40 x 40 x 57 mm)
Enclosure Blue PC+ABS plastic, NEMA type 
Approvals
CSA C US, meets class B: ICES & FCC Part 5
Ambient conditions
Indoor use only, 32 to 22°F (0 to 50°C), RH ≤90% Non-
condensing
Power supply 24 V (ac) ±0%, 60 Hz, 98 VA, Class 2
Zone valve load 24 V (ac) 2 A, maximum combined current (zones  to 4): 4 A
End switch relay 24 V (ac) 2 A
Warranty Limited 3 Year (See D35 for full warranty)
1/2” Knock-out (x 4)
Ø 1/8” (3 mm)
7/8” x 1/2” (23 mm x 12 mm)
Knock-out (x 4)
1/2” x 5/8
(12 mm x 16 mm)
Knock-out (x 4)
2–1/4”
(57 mm)
Input Power: 24 V (ac) ±10% 60 Hz
98 VA Max, Class 2
Control Load: 2 VA
End Switch: 24 V (ac) 2 A
Zone Output: 2 A per zone
4 A (max) total
Power
Zone
1
Zone
2
Zone
3
Zone
4
Zone
5
Zone
6
End Switch
C
Zone 2
WtN4 R C
Zone 3
WtN4 R C
Zone 4
WtN4 R
tN4 Wiring Center 315
Six Zone Valves
W tN4C tN4C X
Zone 1 Expansion
VlvC
Zone 1
VlvC
Zone 2
VlvC
Zone 3
VlvC
Zone 4
VlvC
Zone 5
VlvC
Zone 6
X C
Input Power
RR
W tN4C
Zone 5
RW tN4C
Zone 6
R
H8001
A
End Switch
Made in Canada
tektra 1032-01
Use at least 167°F
(75°C) conductors
Front View Side View Back View

Summary of content (2 pages)