User Interface - Indicator LED
Sequence of Operation
Zone Operation
When a thermostat calls for heat by closing the R and W
terminals:
24 V (ac) is applied to the corresponding zone valve.
The corresponding zone indicator LED is turned on.
Boiler Operation
When a thermostat calls for heat by closing the R and W
terminals:
The boiler end switch XX is closed to fire the boiler.
The RoomResponse
TM
0-10 V (dc) or 4-20 mA signal is sent
to a modulating-condensing boiler.
DHW Operation
Many modulating-condensing boilers have multiple temperature
call inputs. Wire the DHW end switch to input recommended
in the boiler's manual.
When a zone 1 calls for heat by closing the R and W terminals:
The DHW end switch is closed to fire the boiler at the DHW
temperature.
The Mod Boiler output is changed to 10 V (dc) or 20 mA.
Master / Member DIP Switch
Allows for unlimited expansion using additional Switching
Relays and/or Zone Valve Controls.
The Master Switching Relay is wired and operates the boiler.
If using a single Switching Relay set to Master.
When using multiple Switching Relays and/or Zone Valve
Controls, set one control to Master and set all other con-
trols to Member.
T-Stat 1 Priority DIP Switch
When T-Stat 1 is calling for heat by closing the R and W
terminals:
115 V (ac) is applied to the Priority Pump 1.
Zone 1 indicator LED is turned on.
Priority indicator LED is turned on.
Zones 2 to 6 zone valves and LEDs are turned off.
Expansion Member controls shut off their zones.
After 60 minutes of continuous zone 1 call for DHW heating,
zones 2 to 6 are able to turn back on. This prevents building
freeze up if the DHW tank aquastat fails in the closed position.
A jumper wire must be installed on the zone 1 end switch if
a pump is installed and the Zone Valve End Switches DIP
switch is set on.
Exercising DIP Switch
ON: Each circulator pump is energized for 30 seconds every
72 hours.
OFF: Circulator pump exercising disabled.
Post Purge DIP Switch
ON: After thermostat 1 stops calling for heat, the zone 1 priority
pump and zone valve remain on for 2 minutes to purge heat
from the boiler to the zone.
OFF: Post purge disabled.
Mod Boiler DIP Switch
Select either 0-10 V (dc) or 4-20 mA signal to the modulating
condensing boiler. Consult the boiler manual to determine
the signal type. The DIP switch position does not matter if
the modulating boiler output is not used.
System Pump During Priority DIP Switch
On: System pump operates when zone 1 calls for heat.
Off: System pump shuts off when zone 1 calls for heat.
Typically set off when using a pump for heating a domestic
hot water tank.
System Pump With Member Call DIP Switch
On: System pump on the master control runs when a zone
on a member control calls for heat.
Off: System pump on the master control does not turn on
when a zone on a member control calls for heat.
Zone Valve End Switches DIP Switch
On: System pump and boiler will not turn on until the zone
valve end switch is closed. Select this option when using 3
or 4-wire zone valves.
Off: System pump and boiler turn on immediately when a
thermostat calls for heat. Select this option when using 2-wire
zone valves.
Fuses
All fuses are T5A 250V slow blow.
Fuse 1 and 2 correspond to the 24 V (ac) transformer power
supply. If a fuse is blown, first check that the thermostat
wiring is not shorted. Then replace the fuse.
Power
On when 115 V (ac) is applied.
Off when power disconnected or transformer fuse is blown.
Priority
On when zone 1 has priority over zones 2 to 6.
RoomResponse
TM
On when modulating condensing boiler is operating below
maximum setting.
System Pump
On when zone valve end switches are closed (valve open).
Off when zone valve end switches are open circuit (valves closed).
Zone 1 Call
On when thermostat 1 calls for heat.
Off when thermostat 1 stops calling for heat.
Zones 2 to 6 Call
On when the corresponding thermostat calls for heat.
Off during priority operation.
Off when corresponding thermostat stops calling for heat.
Zones 1 to 6 Valve Open
On when corresponding thermostat calls for heat and the
zone valve is open (zone valve end switch closed).
Off when zone valve closed (zone valve end switch open circuit).
Off when corresponding thermostat stops calling for heat.