User Guide
4 of 12
© 2016 tekmar 306V
_
D - 11/16
Application 306V–1
Mechanical
---------------------------------------------------------------------------------------------
Electrical
-----------------------------------------------------------------------------------------------
B1 = Boiler
PS = System Pump
T1 = WiFi Thermostat 561 or 562
T2 to T4 = Thermostat 518 or 519
T5 = Generic Digital Power-Stealing Thermostat
T6 = Generic Bi-Metallic Strip Thermostat
V1 to V6 = 2-Wire Zone Valves
N
B1
PS
306V
V1 V2 V3 V4 V5 V6
DIP Switches
Master
T-stat 1 Priority = On
Exercising = On
Post Purge = On
Mod Boiler = depends on boiler
System Pump During Priority = Off
System Pump With Member Calls = On
Zone Valve End Switches = On
Included resistor must be installed
when using power stealing
thermostats
(e.g. Thermostat T5)
Away C R Rh W Away C R Rh WAway C R Rh W Away C R Rh W R W R W
MOD
X X
tN4
T1 T2 T3 T4 T5 T6
A
DHW C R W
BOILER T-STAT 1 T-STAT 2 T-STAT 3
-
+
tN4
A
C R W
tN4
A
C R W
T-STAT 4
tN4
A
C R W
T-STAT 5
tN4
A
C R W
T-STAT 6 EXPANSION
tN4
A
C R W
tN4
A
B C D E
FUSE 2 FUSE 1
END
SWITCH
MOTOR
POWER
PRIORITY SYS PUMP
ROOM
RESPONSE
ZONE 1
70 80
9060
50 100
MOD MAX %
END
SWITCH
MOTOR
ZONE 2
END
SWITCH
MOTOR
ZONE 3
END
SWITCH
MOTOR
ZONE 4
END
SWITCH
MOTOR
ZONE 5
END
SWITCH
MOTOR
ZONE 6
MASTER MEMBER
OFF
OFF
OFF
T-STAT 1 PRIORITY : ON
EXERCISING : ON
POST PURGE : ON
MOD BOILER : 0-10V
SYSTEM PUMP DURING PRIORITY: ON
SYSTEM PUMP WITH MEMBER CALL: ON
ZONE VALVE END SWITCHES: ON
RESERVED
120 VAC
POWER PUMP PUMP 1
SYSTEM PRIORITY
L N L N L N
OFF
OFF
OFF
4-20 mA
B1
T1
T2 T3 T4 T5 T6
PS
V1 V2 V3 V4 V5 V6
L N
The Zone Valve Control 306V operates six heating zones. When the thermostat calls for heat, the zone valve opens, the system
pump is turned on and the boiler is fired.