Install the Bosch ICM as per the directions.
Set ICM jumper to the left position to enable system supply
water temperature (VT) mode.
Install the Buderus EM10 module as per the directions.
Do NOT install the jumper between U terminals 1 and 3 on
the EM10 module.
Change control to mode 6 in the control parameters.
Move jumper on connection board from A to B.
Set function 17 to temperature.
Change Parameter 9 Remote 4-20 mA to Setpoint Source.
Change "Energy Management" setting "Central Heat
Modulation Source" to 4-20 mA.
Change "Energy Management" setting "Central Heat 4-20
mA Setup, 4 mA Water Temperature" to 80°F (26.5°C).
+
9
+
10
+
22
+
23
+
5
+
6
+
16
17
+
+
2
U
1
+
X
X
T
T
+
1 2 9 10
No changes to the boiler are required.
Aerco AM Series
--------------------------------
Bosch Greenstar
-------------------------------
Buderus GB142 and GB162
----------------------
Burnham Alpine
---------------------------------
Camus Modulating MicoFlame
------------------
Heat Transfer Products Elite
---------------------
IBC VFC and SL Series
--------------------------
Laars Mascot LX
--------------------------------
On the V10 controller:
Set Load 1 to External Control
Change "Max Control @ 9.5 Vdc" to 190°F (88°C)
Change "Min Control @ 2.1 Vdc" to 32°F (0°C)
IBC V10
Control
304V
+
X
X
T
T
+
1 2 9 10
Change Installer Parameter 25 "0-10V to Power" to Disabled.
Change Installer Parameter 26 "0-10V to outlet setpoint" to
Disabled.
Laars
Mascot LX
304V
+
X
X
T
T
+
5 6 11 12