No changes to the boiler are required.
Install the Peerless PFA-1 Interface Adapter
On the boiler display, change Central Heating Mode to 4 for
0-10 VDC Input to Modulate Setpoint
Set boiler PIM DIP switch 2 to Off.
Set boiler PIM DIP switch 5 to On.
Set boiler PIM DIP switch 6 to Off.
Set APP parameter to EMS
Set SIGNAL parameter to 0-10Vdc
Set SETP LO to 70°F
Set SETP HI to 180°F
Set BMS Type to Setpoint. This is the factory default setting.
Set BMS parameter to ACTIVE.
Set BMS Type to SETPOINT.
Enter boiler password.
Set Parameter "Setpoint source" to 4-20mA
Enter boiler password.
Set Parameter "Setpoint source" to 4-20mA
Lochinvar
Knight
Lochinvar
FTXL
NTI Trinity LX
Riverside
HeatStation
NTI Trinity Fire Tube
304V
304V
304V
304V
304V
Sensor I/O
24Vac I/O
+
X
X
W
R
+
19 20 33 34
+
X
X
W
R
+
21 22 35 36
+
X
X
CH1
R
+
3 5 11 12
+
X
X
CH1
R
+
3 5 4 5
+
+
8
EMS
9
Laars
Mascot FT
Peerless
Pinnacle
Terminal Strip
Peerless
Pinnacle
Control Board
Peerless
PFA-1 Interface
Adapter
304V
304V J5 J8 J18
+
16
17
+
+
15
+
16
2
8
+
1 2 1 2
Laars Mascot FT
--------------------------------
Lochinvar Knight
--------------------------------
Lochinvar FTXL
---------------------------------
NTI Trinity LX
------------------------------------
NTI Trinity FireTube
------------------------------
Peerless Pinnacle PF-200, 210, 300, 399
---------
Riverside HeatStation
---------------------------