Install Instructions

9 of 12
Bosch ICM
Aerco AM
Camus Micoflame
HTP Elite
Buderus EM10 Module
Burnham Alpine
303V
303V
303V
303V
303V
303V
Install the Bosch ICM as per the directions.
Set ICM jumper to the left position to enable system
supply water temperature (VT) mode.
Install the Buderus EM10 module as per the directions.
Do NOT install the jumper between U terminals 1 and
3 on the EM10 module.
Change control to mode 6 in the control parameters.
Move jumper on connection board from A to B.
Set function 17 to temperature.
Change Parameter 9 Remote 4-20 mA to Setpoint
Source.
Change "Energy Management" setting "Central Heat
Modulation Source" to 4-20 mA.
Change "Energy Management" setting "Central Heat 4-20
mA Setup, 4 mA Water Temperature" to 80°F (26.5°C).
+
9
+
10
+
22
+
23
+
5
+
6
+
16
17
+
+
2
U
1
+
X
X
TT +
12
91
0
No changes to the boiler are required.
On the V10 controller:
Set Load 1 to External Control
Change "Max Control @ 9.5 Vdc" to 190°F (88°C)
Change "Min Control @ 2.1 Vdc" to 32°F (0°C)
IBC V10 Control303V
+
X
X
TT +
12
91
0
Change Installer Parameter 25 "0-10V to Power" to
Disabled.
Change Installer Parameter 26 "0-10V to outlet
setpoint" to Disabled.
Laars Mascot LX303V
+
X
X
TT +
5611 12
Aerco AM Series Camus Modulating MicoFlame
Heat Transfer Products Elite
IBC VFC and SL Series
Bosch Greenstar
Buderus GB142 and GB162
Burnham Alpine Laars Mascot LX