Install Instructions

10 of 12
No changes to the boiler are required.
Install the Peerless PFA-1 Interface Adapter
On the boiler display, change Central Heating Mode
to 4 for 0-10 VDC Input to Modulate Setpoint
Set boiler PIM DIP switch 2 to Off.
Set boiler PIM DIP switch 5 to On.
Set boiler PIM DIP switch 6 to Off.
Set APP parameter to EMS.
Set SIGNAL parameter to 0-10Vdc.
Set SETP LO to 70°F.
Set SETP HI to 180°F.
Set BMS Type to Setpoint. This is the factory default
setting.
Set BMS parameter to ACTIVE.
Set BMS Type to SETPOINT.
Enter boiler password.
Set Parameter "Setpoint source" to 4-20mA
Enter boiler password.
Set Parameter "Setpoint source" to 4-20mA