Application Brochure

1 of 4 © 2007 A 279 - 12/07
A 279
12/07
- Application Brochure
Steam Control 279
Electrical
Application A 279-1
System Description: The Steam Control 279 regulates the indoor temperature based on firing time of the steam boiler.
The firing time of the steam boiler is based on outdoor temperature, condensate return temperature and control settings.
The condensate return sensor provides information to the control to determine when the boiler has produced enough
steam to reach the furthest radiator and to start the percent boiler on time.
Mechanical
Concept Drawing: This is only a concept drawing, not an engineered drawing. It is not intended to describe a complete system, nor any particular system. It is up to the
system designer to determine the necessary components for and configuration of the particular system being designed, including additional equipment, isolation relays
(for loads greater than the control’s specified output ratings), and any safety devices which in the judgement of the designer are appropriate, in order to properly size,
configure and design that system and to ensure compliance with building and safety code requirements.
115 V (ac)
F1
A2
T3 T2
S1
S2
T1
Zone 1Zone 2Zone 3
A1
279
N
115 V (ac)
L
S2
S1Boiler
14
Sen
13
S1
12
S2
11
Sen
10
Sen
9
Sen
15
Sen
16
Sen
Do not apply power
279
N
52
Power
L
634 7
Boiler Com Com
DHW
Indr Indr Com Cdn Out
8
Alert 2Alert 1
High Low
1
S1 = Outdoor Sensor 070
S2 = Condensate Sensor 071
T1...T3 = Thermostatic Steam Traps
F1 = Float and Thermostatic Trap
A1, A2 = Main Air Vents
S1 = Outdoor Sensor 070
S2 = Condensate Sensor 071

Summary of content (4 pages)