Boiler Control 274
Electrical
Application A 274-1
System Description: The Boiler Control 274 controls up to four On/Off boilers to provide outdoor reset for the space heating
zones. The boilers are piped in primary-secondary and the primary pumps are controlled by the 274 to allow for redundant
pumping capacity as well as equal run time rotation. The 274 has an alert contact which closes when a pump error occurs.
A flow proof device is used to prove flow from the pumps to the 274.
Mechanical
Concept Drawing: This is only a concept drawing, not an engineered drawing. It is not intended to describe a complete system, nor any particular system. It is up to the
system designer to determine the necessary components for and configuration of the particular system being designed, including additional equipment, isolation relays
(for loads greater than the control’s specified output ratings), and any safety devices which in the judgement of the designer are appropriate, in order to properly size,
configure and design that system and to ensure compliance with building and safety code requirements.
S2F1
A1
P2
P1
120 V (ac)
274
S1
P3
P4 P5
P6
S1 = Outdoor Sensor 070
S2 = Boiler Supply Sensor 082
P1 = Primary Pump
P2 = Stand-by Primary Pump
P3,...,P6 = Boiler Pumps
F1 = Flow Proof Device
A1 = Alert
S2
Boiler
1
S1
6
DHW
5
4
Sup
3
+
2
-
1
Do not apply power
274
N
720
Power
L
8
tN4 Com Out Boil Com BRet/ Relay
1
910
Relay
2
11 12
Relay
3
13 14
Relay
4
15 16
C.A./
Alert
21 22
Boiler
Demand
23 24
DHW
/Setp
Com
Dem
25
Pr.
Dem
19
Prim
P1
18
DHW
/P2
17
Boiler
2
Boiler
3
Boiler
4
P1
N
115 V (ac)
L
A1
P2
F1
Demands
Setback
Off
EMS
Rotate
Fixed Last
Pump Sequencer
Exercise
Off
Fixed Lead
First On / Last Off
First On / First Off
274 Switch Settings:Essential Control Settings:
Mode = 1