Testing the Control
The Boiler Control 260 has a built-in test routine which is used to test
the main control functions. The 260 continually monitors the sensors,
and displays an error message whenever a fault is found. See the
following pages for a list of the 260s error messages and possible
causes. When the
Test
button is pressed, the test light is turned on.
The individual outputs and relays are tested in the following test
sequence.
TEST SEQUENCE
Each step in the test sequence lasts 10 seconds.
During the test routine, the test sequence is paused by pressing the
Test
button. Only if there is a boiler demand can the control be
paused in a step. If the
Test
button is not pressed again for 5 minutes while the test sequence is paused, the control exits the entire
test routine. If the test sequence is paused, the
Test
button can be pressed again to advance to the next step. This can also be used
to rapidly advance through the test sequence. To reach the desired step, repeatedly press and release the
Test
button until the
appropriate device and segment in the display turn on.
Step 1
- The boiler pump (
Boil P1
) is turned on for 10 seconds.
Step 2
- The
Boiler
contact is turned on for 10 seconds. After 10 seconds, the
Boiler
and
Boil P1
contacts are shut off.
Step 3
- If a DHW pump is selected as the DHW device, the
DHW Pmp / Vlv
contact is turned on for 10 seconds and is then shut
off.
- If a DHW valve is selected as the DHW device, the
DHW Pmp / Vlv
and
Boil P1
contacts are turned on for 10 seconds and
then shut off.
Note
: This step can only be paused if a DHW demand is present.
Step 4
- After the test sequence is completed, the control resumes its normal operation.
Adjust Menu (2 of 2)
Section
Advanced
Installer
Display Description Range
Actual
Setting
The systems warm weather shut down during the
unoccupied (Night) period.
35 to 100°F, OFF
(2 to 38°C, OFF)
B3
The units of measurement that all of the
temperatures are to be displayed in the control.
°F, °C
This item exits the ADJUST menu by pressing
either the or button.
ADJUST
WWSD
°
F
OCC
UN
Test
not testing
testing
testing paused
off
red
red
ADJUST
°
F
ADJUST