Wiring Guide

© 2008 W 162 - 12/08 6 of 8
tN4 C R Com S1
12345
tN4 C R W
Zone Manager
Wiring the Setpoint Control
Power 24 V (ac) Terminals 2, 3
Wire 24 V (ac) to terminals C and R.
If a Zone Manager is used:
Connect C on the setpoint control to C on the proper
zone of the Zone Manager.
Connect R on the setpoint control to R on the proper
zone of the Zone Manager.
If a 24 V (ac) transformer is used:
Connect C on the setpoint control to C on the
transformer.
Connect R on the setpoint control to R on the
transformer.
tN4 Communication Terminals 1, 2
Wire the tN4 communication to terminals tN4 and C.
If a Zone Manager is used:
Connect tN4 on the setpoint control to the tN4 on the
proper zone of the Zone Manager. The C terminal is
already connected.
If a Zone Manager is not used:
Connect tN4 on the setpoint control to the tN4 terminal
on another tN4 device on the same tN4 bus.
Connect C on the setpoint control to the C terminal on
another tN4 device on the same tN4 bus.
Setpoint Control
Zone Manager
tN4 C R Com S1
12345
tN4 C R W
Relay 1 and Relay 2 Terminals 6, 7, 8
Relay 1 is used to switch the heat or cooling.
Relay 2 is used to switch the recirculation pump.
If a Zone Manager is used:
Connect Relay 1 to W on the proper zone on the Zone
Manager.
Connect Relay 2 to W on the proper zone on the Zone
Manager.
If a Zone Manger is not used:
Determine if the jumper must be cut.
When the jumper is not cut, Relay 1 and Relay 2 is
internally powered through terminal 3.
When the jumper is cut, Rh and Relay 1 and Relay 2
are isolated switches.
Setpoint Control
Zone Manager
R RhR1R2
3 678
tN4 C R W
Zone Manager
tN4 C R W
Sensor Input Terminals 4, 5
The sensor is connected to the setpoint control on terminals
Com and S1.
Connect sensor to terminals S1 and Com.
Do not apply power
to terminals S1 and Com,
permanent damage to the sensors and / or setpoint
control will result!
Universal
Sensor
Setpoint Control
tN4 C R Com S1
12345
Do Not Apply Power
Setpoint Control