Install Instructions

6 of 8
© 2016 tekmar 087
_
D - 08/16
Resistance Temperature
336095 -40°F (-40°C)
242426 -31°F (-35°C)
176801 -22°F (-30°C)
130307 -13°F (-25°C)
97007 -4°F (-20°C)
72910 5°F (-15°C)
55303 14°F (-10°C)
Resistance Temperature
42316 23°F (-5°C)
32651 32°F (0°C)
25395 41°F (5°C)
19903 50°F (10°C)
15714 59°F (15°C)
12493 68°F (20°C)
10000 77°F (25°C)
Resistance Temperature
8056 86°F (30°C)
6530 95°F (35°C)
5325 104°F (40°C)
4367 113°F (45°C)
3601 122°F (50°C)
2985 131°F (55°C)
2487 140°F (60°C)
10K Type 2 NTC Thermistor (tekmar)
ON
Resistance Temperature
239686 -40°F (-40°C)
179200 -31°F (-35°C)
135185 -22°F (-30°C)
102861 -13°F (-25°C)
78913 -4°F (-20°C)
61020 5°F (-15°C)
47543 14°F (-10°C)
Resistance Temperature
37313 23°F (-5°C)
29490 32°F (0°C)
23457 41°F (5°C)
18780 50°F (10°C)
15130 59°F (15°C)
12263 68°F (20°C)
10000 77°F (25°C)
Resistance Temperature
8194 86°F (30°C)
6752 95°F (35°C)
5592 104°F (40°C)
4655 113°F (45°C)
3893 122°F (50°C)
3271 131°F (55°C)
2760 140°F (60°C)
10K Type 3 NTC Thermistor
ON
Sensor Resistance Settings
DIP switches in the right side of the wiring chamber are configured to match the
sensor requirements of the connected control.
'10K Type 2' is the default setting that works with all tekmar controls and thermostats
with outdoor sensor inputs. Other vendor products are listed below:
Setting
Boilers Controls
5k
Viessmann Vitodens-100W WB1B
Heat Timer (excl. EPU-CH)
10k Type 2
Laars Mascot
Laars Neotherm
Viessmann
(incl. Vitodens 100W
B1HA & B1KA)
Lochinvar
Camus
ATH
Navien
Allied SG, AAA and
Electric
IBC SL,VFC
Slant/Fin CHS
NTI Trinity & Vmax
Raypak
RBI
Smith Boiler
tekmar reset controls and
thermostats
Honeywell AQ2000
Uponor CCN
10k Type 3
Buderus GB Series Taco iWorx
12k
Peerless Purefire
IBC DC & HC
Series
Triangle Tube
Prestige Solo &
ACVMax
HTP Elite
Allied HSE
Bosch Greenstar
Weil-McLain Ultra
Series 3, Evergreen
& 97+
Slant/Fin Lynx
Slant/Fin Jaguar
20k
Honeywell Building Controls