Performance Data Sheet
Sept. 5, 2014
Revision: REL
Celseon® Air Cooled Condensing Unit
Model: AKA4460YXCDJ
BoM: 2G232-79 R-134a 1/2 HP
Model
Dimensions, inches
Line Connection*
Pumpdown
Air
Oil Ch
Gr. Wt.
L
W
H
CH
Suction
Liquid
90 °F 90%
SCFM
Oz.
Lbs.
AKA4460YXCDJ
20.0
14.3
12.1
10.1
5/8” S
3/8” S
3.2 lbs
230
17
54
* F = Flare, S = Solder, RF or RS = Rotolock with Flare or Solder Connections, C = Compression Fitting
Factory charge: 20 PSIG Nitrogen – MUST BE EVACUATED
Ambient Temperatures
Evaporator T, 80°F 90°F 100°F 110°F
°F
PSIG
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
20
18.4
4060
692
105
3658
691
114
3249
697
122
2867
695
131
25 22.1 4526 742 108 4098 751 117 3655 757 123 3252 756 133
30
26.1
5005
793
112
4546
814
120
4071
820
125
3633
823
136
35
30.4
5500
849
115
5003
877
124
4495
887
128
4008
895
140
40 35.1 6007 907 118 5468 941 127 4928 957 133 --- --- ---
45
40.1
6528
969
122
5940
1007
130
5370
1031
140
---
---
---
50
45.5
7062
1034
125
6420
1073
133
---
---
---
---
---
---
55 51.3 7611 1102 129 6910 1141 137 --- --- --- --- --- ---
50 Hz Performance
Return gas temp. 65°F, 5°F sub cooling