Performance Data Sheet
Sept. 18, 2014
Revision: REL
Celseon® Air Cooled Condensing Unit
Model: AJB7465ANAD*
BoM: 2G745-** R-12 3/4 HP
Large Capacity Pump Down Unit
Model
Dimensions, inches
Line Connection*
Pumpdown
Air
Oil Ch
Gr. Wt.
L
W
H
CH
Suction
Liquid
90 °F 90%
SCFM
Oz.
Lbs.
AJB7465ANADC
20.0 14.3 12.1 11.6
5/8” S
3/8” S
7.2 lbs
230 22
64
AJB7465ANADP
5/8” S
3/8” S
7.2 lbs
64
* F = Flare, S = Solder, RF or RS = Rotolock with Flare or Solder Connections, C = Compression Fitting
Factory charge: 20 PSIG Nitrogen – MUST BE EVACUATED
Ambient Temperatures
Evaporator T, 90°F 100°F 110°F
°F
PSIG
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
0 9.2 4260 870 121 4020 890 124 3780 910 127
10
14.6
5355
1000
125
5110
1020
128
4830
1040
132
15
17.7
5960
1085
127
5690
1110
130
5450
1130
133
20 21.0 6560 1180 129 6300 1210 133 6080 1230 136
25
24.6
7200
1280
132
6880
1315
135
6600
1350
138
30
28.4
7650
1400
135
7510
1435
138
7190
1470
142
60 Hz Performance
Return gas temp. 40°F, 5°F sub cooling