Performance Data Sheet

Sept. 18, 2014
Revision: REL
Celseon® Air Cooled Condensing Unit
Model: AJA7455YNAD*
BoM: 2G743-** R-134a 3/4 HP
Large Capacity Pump Down Unit
Model
Dimensions, inches
Line Connection*
Pumpdown
Air
Oil Ch
Gr. Wt.
L
W
CH
Suction
Liquid
90 °F 90%
SCFM
Oz.
Lbs.
AJA7455YNADC
20.0 14.3 12.1 11.6
5/8” S
3/8” S
6.6 lbs
230 26
64
AJA7455YNADP
5/8” S
3/8” S
6.6 lbs
64
* F = Flare, S = Solder, RF or RS = Rotolock with Flare or Solder Connections, C = Compression Fitting
Factory charge: 20 PSIG Nitrogen MUST BE EVACUATED
Ambient Temperatures
Evaporator T, 80°F 90°F 100°F 110°F
°F PSIG BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T
-10
1.9
2755
640
96
2438
634
105
2035
609
113
1651
574
121
-5
4.2
3286
709
99
2913
697
108
2470
677
116
2063
654
124
0 6.5 3831 781 102 3405 769 111 2926 754 119 2492 738 127
5
9.1
4388
858
106
3914
850
115
3401
837
122
2938
825
130
10
11.9
4958
939
110
4439
938
118
3896
929
125
3401
916
133
15 15.0 5542 1024 113 4981 1035 122 4412 1028 129 3882 1010 137
20
18.4
6138
1114
117
5540
1140
125
4947
1135
133
4380
1108
141
25
22.1
6747
1208
121
6116
1253
129
5502
1250
137
---
---
---
30 26.1 7370 1305 125 6709 1375 133 6077 1372 141 --- --- ---
35 30.4 8005 1408 129 7318 1504 137 --- --- --- --- --- ---
60 Hz Performance
Return gas temp. 40°F, 5°F sub cooling