Performance Data Sheet
January 23, 2013
Revision: REL
Celseon® Air Cooled Condensing Unit
Model: AJA4512ANAD*
BoM: 2G1020-** R-12 1 HP
Model
Dimensions, inches
Line Connection*
Pumpdown
Air
Oil Ch
Gr. Wt.
L
W
H
CH
Suction
Liquid
90 F 90%
SCFM
Oz.
Lbs.
AJA4512ANADA
24.0
17.6
13.4
11.8
3/8” S
3/8” S
N/A
270
22
76
AJA4512ANADG
3/8” S
3/8” S
7.8 lbs
77
AJA4512ANADH
3/8” S
3/8” S
N/A
76
AJA4512ANADK
3/8” S
3/8” S
76
AJA4512ANADC
3/8” S
3/8” S
7.8 lbs
77
AJA4512ANADS
3/8” S
3/8” S
N/A
76
AJA4512ANADJ
3/8” S
3/8” S
7.8 lbs
78
AJA4512ANADP
3/8” S
3/8” S
7.8 lbs
78
* F = Flare, S = Solder, RF or RS = Rotolock with Flare or Solder Connections, C = Compression Fitting
Factory charge: 20 PSIG Nitrogen – MUST BE EVACUATED
Ambient Temperatures
Evaporator T,
90°F
100°F
110°F
°F
PSIG
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
20
21.0
7400
1250
118
7050
1290
127
6700
1330
135
25
24.6
8200
1340
121
7800
1380
130
7400
1415
138
30
28.5
8900
1430
123
8600
1470
132
8000
1505
140
40
37.0
10780
1620
127
10200
1660
137
9600
1700
145
45
41.7
11780
1725
130
11150
1765
138
10500
1810
146
50
46.7
12780
1830
131
12150
1880
139
11600
1925
147
60 Hz Performance