Performance Data Sheet

Sept. 18, 2014
Revision: REV
Celseon® Air Cooled Condensing Unit
Model: AJA4488AAAD*
BoM: 2G748-** R-12 3/4 HP
Large Capacity Pump Down Unit
Model
Dimensions, inches
Line Connection*
Pumpdown
Air
Oil Ch
Gr. Wt.
L
W
CH
Suction
Liquid
90 °F 90%
SCFM
Oz.
Lbs.
AJA4488AAADC
20.0 14.3 12.1 12.0
5/8” S
3/8” S
7.2 lbs
230 22
64
AJA4488AAADP
5/8” S
3/8” S
7.2 lbs
64
* F = Flare, S = Solder, RF or RS = Rotolock with Flare or Solder Connections, C = Compression Fitting
Factory charge: 20 PSIG Nitrogen MUST BE EVACUATED
Ambient Temperatures
Evaporator T, 90°F 100°F 110°F
°F PSIG BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T
20
21.0
5800
1020
114
5450
1050
121
5100
1070
129
25
24.6
6380
1085
116
6000
1120
123
5650
1145
131
30 28.5 6950 1150 117 6550 1190 125 6200 1220 132
40
37.0
8200
1290
121
7800
1330
129
7400
1380
137
45
41.7
8800
1360
123
8400
1400
131
8000
1460
139
50 46.7 9500 1430 125 9050 1480 133 8600 1540 142
60 Hz Performance
Return gas temp. 65°F, 5°F sub cooling

Summary of content (3 pages)