Performance Data Sheet

Sept. 18, 2014
Revision: REL
Celseon® Air Cooled Condensing Unit
Model: AJA4480YAAD*
BoM: 2G746-** R-134a 3/4 HP
Large Capacity Pump Down Unit
Model
Dimensions, inches
Line Connection*
Pumpdown
Air
Oil Ch
Gr. Wt.
L
W
CH
Suction
Liquid
90 °F 90%
SCFM
Oz.
Lbs.
AJA4480YAADC
20.0 14.3 12.1 12.0
5/8” S
3/8” S
6.6 lbs.
230 26
64
AJA4480YAADP
5/8” S
3/8” S
6.6 lbs.
64
* F = Flare, S = Solder, RF or RS = Rotolock with Flare or Solder Connections, C = Compression Fitting
Factory charge: 20 PSIG Nitrogen MUST BE EVACUATED
Ambient Temperatures
Evaporator T, 80°F 90°F 100°F 110°F
°F PSIG BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T
20
18.4
5305
875
112
4791
878
120
4300
881
128
3829
884
135
25
22.1
5883
946
116
5328
954
123
4796
962
131
4287
970
139
30 26.1 6467 1022 120 5871 1035 127 5298 1047 135 4749 1060 142
35
30.4
7051
1101
124
6413
1119
131
5800
1136
138
---
---
---
40
35.1
7631
1184
127
6950
1207
135
6294
1229
142
---
---
---
45 40.1 8201 1271 131 7550 1298 139 --- --- --- --- --- ---
50 45.5 8756 1362 135 7988 1394 142 --- --- --- --- --- ---
60 Hz Performance
Return gas temp. 65°F, 5°F sub cooling

Summary of content (3 pages)