Performance Data Sheet
March 7, 2014
Revision: B
Celseon® Air Cooled
Condensing Unit
Model: AE4460Y-AA3CD*
BoM: 2G227-** R-134a 1/2 HP
Model
Dimensions, inches
Line Connection*
Pumpdown
Air
Oil Ch
Gr. Wt.
L
W
H
CH
Suction
Liquid
90 °F 90%
SCFM
Oz.
Lbs.
AE4460Y-AA3CDA
20.0 14.3 12.1 9.3
3/8” S
1/4” S
N/A
270 9.5
45
AE4460Y-AA3CDG
3/8” S
3/8” S
3.2 lbs
47
AE4460Y-AA3CDH
3/8” S
3/8” S
N/A
45
AE4460Y-AA3CDK
3/8” S
1/4” S
45
AE4460Y-AA3CDC
3/8” S
3/8” S
3.2 lbs
47
AE4460Y-AA3CDS
3/8” S
3/8” S
N/A
45
AE4460Y-AA3CDJ
3/8” S
3/8” S
3.2 lbs
47
AE4460Y-AA3CDP
3/8” S
3/8” S
3.2 lbs
47
* F = Flare, S = Solder, RF or RS = Rotolock with Flare or Solder Connections, C = Compression Fitting
Factory charge: 20 PSIG Nitrogen – MUST BE EVACUATED
Ambient Temperatures
Evaporator T, 80°F 90°F 100°F 110°F
°F
PSIG
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
5 9.0 2511 517 95 2315 530 104 2125 544 114 1941 558 123
10
11.9
2856
545
97
2650
560
106
2449
575
116
2253
590
125
15
15.0
3221
573
99
3004
590
108
2790
607
118
2580
624
127
20 18.4 3719 614 101 3494 633 110 3271 653 120 3050 672 129
25
22.1
4134
646
103
3895
667
113
3657
688
122
3419
710
131
30
26.1
4563
679
106
4308
702
115
4053
725
125
3797
748
134
35 30.4 5003 713 108 4731 737 118 4457 762 127 4181 787 136
40
35.0
5452
748
111
5160
774
120
4866
801
130
4568
828
139
45 40.1 5905 784 114 5593 812 123 5277 841 132 --- --- ---
60 Hz Performance
Return gas temp 40°F below 20°F evaporator,