User’s manual  UPS EVO DSP PLUS TT
."$
Voltage Range Lower Limit: 5÷10 % (selectable); upper Limit: 5÷10 % (selectable)
Frequency Range (50 Hz) Lower Limit: 46÷48 Hz (selectable); upper Limit: 52÷54 Hz (selectable
Frequency Range (60 Hz) Lower Limit: 56÷58 Hz (selectable); upper Limit: 62÷64 Hz (selectable
7/#
Battery Type Lead acid, sealed, free maintenance
Number of batteries 20/40 40 60
Nominal Battery Voltage 240 Vdc
Battery Charge Time (typical) 68 hours
Expandable Autonomy Available, through external Battery Box (optional)
;#/;";.;##;
Storage Temperature Range 25°C to +55°C (15°C to 40°C recommended for longer Battery life)
Operating Temperature Range 0°C to +40°C (20°C to 25°C recommended for longer Battery life)
Relative Humidity Range 0%  95% (non condensing)
Max. Altitude 3000 m
Protection level IP 20
Cooling Fan cooling
Audible Noise (at 1 meter) < 58 dBA < 60 dBA
;/
Safety EN 6204011, EN 609501
Performance EN 620403
EMC EN 620402 category C3
Product certification CE
."";#.#;
Computer Interface 1 RS232 port and 1 USB port
Software
Included UPS Management Software,
compatible with: Windows, Mac OS X, Linux, Unix, etc.
SNMP Interface Optional
</
EPO (Emergency Power OFF) Included
Dry Contact Interface Optional
Manual Bypass for Maintenance Included
Parallel Operating Mode Optional (up to 3 UPS)
ECO Mode Selectable
Frequency Converter Mode Selectable