User`s manual

;-#<
User’s manual 5 UPS EVO DSP PLUS TT
1) Turn OFF each UPS one by one (by pressing 44 button) and after all of them transfer to Bypass mode, turn
“ON” the external Output circuit breaker of each unit.
3) Turn ON the UPS one by one (by pressing ; button).
5)5) $$(!! 
The steps for correct operation are explained below.
) You can not add one new unit into the Parallel System when whole System is running. You must cut off the
load and shutdown the System.
) Make sure the new unit is a Parallel model, and install the new unit following the instruction of the previous
section.
5)5) / 6* (!! 
The steps for correct operation are explained below. Note: this procedure permits to remove one UPS without
interruption of Output power
You can not remove one unit of the Parallel System when whole System is running in Normal mode.
) Turn OFF the unit (by pressing 44 button for more than 0,5 second). Then the UPS will enter in Bypass
mode or NoOutput mode without output.
) Turn off the output breaker of this unit, then turn off the input breaker of this unit.
) After it shuts down, you can turn off the Battery Box Breaker (only if there is an external Battery Box).
0) Remove the parallel and shared current cables.
) Then remove the unit from the Parallel System.
2 . ,!#*!,
The UPS is factoryequipped with /!$7. ,!#*!,. On the UPS rear side there are the
connections of the Interfaces.
Only one of the RS232/USB communications can be activated at one time. To activate RS232 communication it is
sufficient to connect the RS232 cable only; to activate USB communication it is sufficient to connect the USB cable
only.
Connecting to the Web site ),!), it is possible to download free of charge the updated UPS
Management Software.
It is possible to use a ;"B';>"!!' ,C#*!, to connect the UPS to a LAN (Local
Area Network). The SNMP interface is optional.
We advise you to follow the steps below explained to install the interface correctly:
) Remove the metallic panel (#6, figure 4) that covers the slot for SNMP interface.
) Put the SNMP Interface into the slot and fix it with screws.
) Connect the LAN cable to SNMP interface and follow the included instruction to make the interface working
well.