User`s manual

ENGLISH
User’s manual 18 UPS EVO DSP PLUS MM
10 Technical Characteristics
UPS EVO DSP PLUS MM Model 1.2 2.4 3.6
Power 1200 VA 2400 VA 3600 VA
Nominal Active Power 840 W 1680 W 2520 W
Power Factor 0.7
Technology On-Line Double Conversion Transformerless
Dimension (W x H x D) 14,5 x 22 x 28,2 cm 14,5 x 22 x 39,7 cm 19 x 31,8 x 42,1 cm
Net Weight 10 kg 17 kg 27
INPUT
Nominal Voltage Single Phase 200/208/220/230/240 Vac
Voltage Range
for Normal mode
Lower Limit (transfer
to Battery mode)
110 Vac ± 5% (at 0-60% load)
120 Vac ± 5% (at 60-70% load)
140 Vac ± 5% (at 70-80% load)
160 Vac ± 5% (at 80-100% load)
Lower Limit (come
back to Line mode)
175 Vac ± 5%
Upper Limit (transfer
to Battery mode)
300 Vac ± 5%
Upper Limit (come
back to Line mode)
290 Vac ± 5%
Nominal Frequency 50/60 Hz (automatic selection)
Frequency Range (Normal mode) 47 ~ 53 Hz / 57 ~ 63 Hz
Input Power Factor 0.99 (at 100% Load)
OUTPUT
Nominal Voltage Single Phase 200/208/220/230/240 Vac (selectable)
Voltage Regulation ±2%
Inverter Waveform True Sinewave
Nominal Frequency 50/60 Hz (selectable)
Free Running Frequency (Battery mode) (50 Hz ± 0.25%) or (60 Hz ± 0.25%)
Total Harmonic Distortion (THD) < 3% (Linear Load); < 6% (Non-Linear Load)
Crest Factor 3:1 max
Overload (100÷110)% only acoustic alarm ; (110÷130)% for 30 sec; > 130% per 100 ms
Transfer Time
(Normal <--> Battery) 0 ms
(Battery <--> Bypass) 4 ms (typical)
Efficiency 92% (On-Line mode) ; 98% (ECO mode)
93% (On-Line mode) ; 98%
(ECO mode)
BATTERIES
Battery Type Lead acid, sealed, free maintenance
Number of batteries 2 4 6
Nominal Battery Voltage 24 Vdc 48 Vdc 72 Vdc
Battery Specifications 12 Vdc – 9 Ah
Backup Time (typical) 8 min
Battery Charge Time (typical) 4 hours