Operation Manual
example, if the high temperature alarm is set to +25°C and the
current value moves to +25°C, the alarm will be activated (if it
has been enabled). Now when the temperature drops to
+24.9°C or below and thereafter again increases to beyond
+25°C, the data will be blinking, but no alarm will be activated.
It has to drop to below +24°C (with a pre-set hysteresis of
1°C) so that the alarm can be produced again. Hysteresis
values for the various weather data types are given in the
following table:
Weather data Hysteresis
Temperature 1°C
Humidity 3% RH
Air pressure 1 hPa
Rainfall 24h 5.0mm
Rainfall 1h 0.5mm
Wind 10 km/h
16. Auto memory for stored values
The base station has a memory back up system, which is
used to memorize user-defined settings for when the batteries
are changed or if a power failure occurs. User defined units
are automatically updated each time these are changed. The
base station will memorize the following user defined units:
• Time zone
• 12/24h time display mode
• Unit settings (temperature, pressure, rainfall, wind)
• Air pressure offset for calculation of relative air pressure
• Weather picture threshold
• Storm warning threshold
• LCD contrast
• Alarm time
• Weather Alarm thresholds
• State of alarms (enabled/disabled)
• Rainfall total value and reset time/date
84