PM062 REV 5 08/05/05  4  Thomson Technology 
To change the transfer switch voltage, refer to “INSTRUCTIONS TO CHANGE SYSTEM 
VOLTAGE  ON  TS870  SERIES  TRANSFER  SWITCHES  WITH  TSC  80 
CONTROLLER”  (attached  as  “Appendix  B).    Contact  Thomson  Technology  for  further 
information as may be required. 
3.4.  SYSTEM PHASING-HIGH LEG DELTA SYSTEMS 
For systems using high leg delta 240V 3 phase 4 wire systems, connection of supply 
conductors must have the correct phasing as shown below. 
WARNING 
Failure  to  match  correct  system 
phasing  will  result  in  serious  damage 
to the TSC 80 controller.  
208V
B
(O range)
(High Leg)
C
(Yellow)
A
(R ed)
N
(W hite)
PH A
(UA)
Automatic Transfer
Switch (Utility Supply)
PH B
(UB)
PH C
(UC)
Neural
(N)
120V 120V
240V 240V
Where  transfer  switches  are  supplied  without  power  isolation  transformers  (PT1  & 
PT2) for ATS control logic it is essential that the orientation of phase conductors of 