User guide
TS 870 TRANSFER SWITCH 
PM062 REV 5 08/05/05  2  Thomson Technology 
ventilated  area  free  of  corrosive  agents  including  fumes,  salt  and  concrete/cement 
dust. Apply heat as necessary to prevent condensation. 
2.1.2.  EQUIPMENT OPERATING 
The transfer switch shall be operated in an environment with a temperature range not 
exceeding  +5° to +122° Fahrenheit (-15° to +50° Celsius) and a humidity range not 
exceeding 5%-95% non-condensing. 
3.  NOTES TO INSTALLER 
DANGER!!!! 
Arc Flash and Shock Hazard. Will cause severe injury or death. 
Do not open equipment until ALL power sources are disconnected 
This equipment must  be installed and serviced only by qualified electrical 
personnel  utilizing safe  work  practices  and  appropriate Personal  Protective 
Equipment (PPE). Failure to do so may cause personal injury or death 
3.1.  UPSTREAM CIRCUIT PROTECTIVE DEVICES/ELECTRICAL 
CONNECTIONS 
To  ensure  satisfactory  installation  of  this  equipment  be  sure  to  observe  "Cable  Terminal 
Information”  regarding  power  cable  connection  tightness  and  "Requirements  for  Upstream 
Circuit Protective Devices" located in this manual. 
All mechanical and electrical connections must be checked for tightness prior to placing this 
equipment  in  service  to  ensure  proper  operation  and  to  validate  applicable  warranty 
coverage. 