User guide
TS 870 TRANSFER SWITCH 
PM062 REV 5 08/05/05  28  Thomson Technology 
16.2.  INTERRUPTING CAPACITY CURRENT RATINGS (ALL MODELS WITH 
INTEGRAL OVERCURRENT PROTECTION OPTION) 
INTERRUPTING CAPACITY CURRENT RATING AMPS (RMS)
 1
No Upstream Circuit Breaker Protection Required 
BASIC MODEL 
MAX. 
VOLTAGE 
RATED 
CURRENT 
(A) 
@240V  @480V  @600V 
TS87xA-0100 
600  100  65,000  25,000  14,000 
TS87xA-0150 
600  150  65,000  25,000  14,000 
TS87xA-0200 
240  200  65,000  N/A  N/A 
TS87xA-0250 
600  250  65,000  35,000  22,000 
TS87xA-0400 
600  400  65,000  50,000  25,000 
TS87xA-0600 
600  600  65,000  50,000  25,000 
TS87xA-0800 
600  800  65,000  50,000  25,000 
TS88xA-1000/1200 
600  1000/1200  65,000  50,000  50,000 
1.
Standard ratings only are shown. Consult Thomson Technology for versions with higher interrupting capacity current ratings. 
2.
For other model types not shown, contact Thomson Technology for further information. 
17.  GROUND FAULT SITE TEST REQUIREMENTS 
Per  NEC  and  UL1008,  a  ground  fault  protected  system  shall  be  performance  tested  when  first 
installed  on  site.    A  written  record  of  this  shall  be  made  and  be  available  to  the  authority  having 
jurisdiction. A form is provided at the back of this manual for this purpose – see Section 21. 
Confirm  and  record  actual  trip  setpoints  in  the  form  provided  which  is  to  be  made  available  on 
request by inspection authority. 
17.1.  PERFORMANCE TEST 
Qualified Field Service technicians require a calibrated current injection test apparatus and 
must  be  knowledgeable  in  breaker  testing  to  provide  primary  neutral CT  injection  up  to  or 
greater than the trip setpoint as selected by the responsible party.  As indicated in the NEC, 
the maximum setting of  the ground fault protection shall be 1200 amps, and the maximum 
time delay shall be 1 second for ground faults equal to or greater than 3000 amps. 
The  inspection  authority  should  be  contacted  to  confirm  actual test  requirements  as  these 
may vary by region or local code requirements. 










