200A, over current protection is non-adjustable thermal-magnetic type trip units. For transfer 
switches rated 400A through 1200A over current protection is adjustable electronic type with 
long time & instantaneous trip unit elements with optional ground fault protection elements. 
Note: Ground fault protection is supplied as standard on 1000A and 1200A transfer switches 
that are used on systems greater than 240V. 
An upstream over current protection device is required on the generator source which feeds 
the TS 870 Transfer Switch if integral over current protection option is not specified on the 
ATS. 
Note: For models of transfer switch with adjustable integral over current protection trip units, 
the  over current  protection must  be  set  prior  to  operation.    The  equipment will be  shipped 
from  the  factory  with  a  long-time  current  setting  of  100%  (of  the  equipment  rating)  and 
maximum instantaneous/short-time current and time delay settings. 
WARNING! 
Do  Not  Energize  this  equipment  until 
device  settings  have  been  verified  to 
ensure  proper  system  protection  & 
coordination. Failure to do so may result 
in equipment failure. 
Refer to Section 4.1 Product Model Code for types of integral over current protection which 
are supplied with the transfer switch. 