User guide
TS 870 TRANSFER SWITCH 
PM062 REV 5 08/05/05  11  Thomson Technology 
switch will immediately return to the utility or generator supply if within normal 
operating limits. 
5.2.4.  ADDITIONAL PROCEDURES 
If the "Service Disconnected" pilot light is not illuminated, the service will not 
have  been  successfully disconnected  and  therefore  it  is  not  safe to  perform 
any maintenance until the following additional procedures are performed: 
DANGER!!!! 
Arc Flash and Shock Hazard. Will cause severe injury or death. 
Do not open equipment until ALL power sources are disconnected 
This equipment must  be installed and serviced only by qualified electrical 
personnel  utilizing safe  work  practices  and  appropriate Personal  Protective 
Equipment (PPE). Failure to do so may cause personal injury or death 
1.  Open the door to the transfer switch using a suitable tool and opening the 
door lock with the key. 
2.  Visually inspect the actual position of the transfer switch mechanism.  If the 
position  of  the  transfer  switch  mechanism  is  clearly  in  the  "neutral  position" 
and  the  load  bus  is  de-energized  on  all  phases,  the  service  has  been 
successfully disconnected. Proceed to Step. 4. 
If the position of the transfer switch mechanism is not in the neutral position or 
the load bus is energized, further procedures are required. 
Note: If the position of the transfer switch mechanism is clearly in the "neutral 
position, the "service disconnected" pilot light may not have illuminated due to 
the following reasons: 
a)  Utility  and  generator  supply  voltages  are  not  present  (the  pilot  light 
requires AC supply voltage to be present). 
b)  The  pilot  light  may  be  burnt  out.    The  bulb  should  be  immediately 
replaced with a suitably rated bulb. 
c)  Failure of one  or more  of the sensing/logic contacts. A qualified 
service  technician  is  required  to  trouble  shoot  this  specific  condition. 
Switch the utility control circuit isolation switch to the de-energized position 