315-4PN33

Error
code
Description
0000h no error
809Ah Interface not found e. g. interface is used by PROFIBUS
In the VIPA SLIO CPU with FeatureSet PTP_NO only the
ASCII protocol is configurable. If another protocol is
selected the FC/SFC216 also left with this error code.
8x24h Error at FC/SFC-Parameter x, with x:
1: Error at PROTOCOL
2: Error at PARAMETER
3: Error at BAUDRATE
4: Error at CHARLENGTH
5: Error at PARITY
6: Error at STOPBITS
7: Error at FLOWCONTROL
809xh Error in FC/SFC parameter value x, where x:
1: Error at PROTOCOL
3: Error at BAUDRATE
4: Error at CHARLENGTH
5: Error at PARITY
6: Error at STOPBITS
7: Error at FLOWCONTROL
8092h Access error in parameter DB (DB too short)
828xh Error in parameter x of DB parameter, where x:
1: Error 1. parameter
2: Error 2. parameter
...
6.5 Communication
6.5.1
Overview
The communication happens via the send and receive blocks FC/
SFC 217 (SER_SND) and FC/SFC 218 (SER_RCV). The FCs/SFCs
are included in the consignment of the CPU.
6.5.2 FC/SFC 217 - SER_SND
This block sends data via the serial interface. The repeated call of the
FC/SFC 217 SER_SND delivers a return value for 3964R, USS and
Modbus via RETVAL that contains, among other things, recent infor-
mation about the acknowledgement of the partner station.
The protocols USS and Modbus require to evaluate the receipt tele-
gram by calling the FC/SFC 218 SER_RCV after SER_SND.
Description
VIPA System 300SDeployment PtP communication
Communication> FC/SFC 217 - SER_SND
HB140 | CPU | 315-4PN33 | GB | 14-43 88