315-4PN33

DBB4: CharTimeout WORD (Char. delay time)
DBW6: ConfTimeout WORD (Acknowledgement delay time )
Data block at USS
DBW0: Timeout WORD (Delay time)
Data block at Modbus master
DBW0: Timeout WORD (Respond delay time)
Velocity of data transfer in bit/s (baud)
04h: 1200baud 05h: 1800baud 06h: 2400baud 07h: 4800baud
08h: 7200baud 09h: 9600baud 0Ah: 14400baud 0Bh: 19200baud
0Ch: 38400baud 0Dh: 57600baud 0Eh: 115200baud
Number of data bits where a character is mapped to.
0: 5bit 1: 6bit 2: 7bit 3: 8bit
The parity is -depending on the value- even or odd. For parity control,
the information bits are extended with the parity bit, that amends via
its value ("0" or "1") the value of all bits to a defined status. If no parity
is set, the parity bit is set to "1", but not evaluated.
0: NONE 1: ODD 2: EVEN
The stop bits are set at the end of each transferred character and
mark the end of a character.
1: 1bit 2: 1.5bit 3: 2bit
The parameter FLOWCONTROL is ignored. When sending RTS=1,
when receiving RTS=0.
Return values send by the block:
BAUDRATE
CHARLEN
PARITY
STOPBITS
FLOWCONTROL
RETVAL FC/SFC 216
(Return values)
VIPA System 300S Deployment PtP communication
Parametrization > FC/SFC 216 - SER_CFG
HB140 | CPU | 315-4PN33 | GB | 14-43 87