315-4PN33

Pin RS485
8 RxD/TxD-N (Line A)
9 n.c.
6.4 Parametrization
6.4.1
FC/SFC 216 - SER_CFG
The parametrization happens during runtime deploying the FC/SFC
216 (SER_CFG). You have to store the parameters for STX/ETX,
3964R, USS and Modbus in a DB.
Parameter Declaration Data type Description
PROTOCOL IN BYTE 1=ASCII, 2=STX/ETX, 3=3964R
PARAMETER IN ANY Pointer to protocol-parameters
BAUDRATE IN BYTE Number of baudrate
CHARLEN IN BYTE 0=5bit, 1=6bit, 2=7bit, 3=8bit
PARITY IN BYTE 0=Non, 1=Odd, 2=Even
STOPBITS IN BYTE 1=1bit, 2=1.5bit, 3=2bit
FLOWCONTROL IN BYTE 1 (fix)
RETVAL OUT WORD Return value (0 = OK)
Connection
Description
Parameters
VIPA System 300S Deployment PtP communication
Parametrization > FC/SFC 216 - SER_CFG
HB140 | CPU | 315-4PN33 | GB | 14-43 85