315-4PN33

Event-ID Description
0xEAA0 Emac Error occurred
OBNo: Current PLC mode
ZInfo1: Diagnostics address of the master / controller
ZInfo2:
0: None Rx queue is full
1: No send buffer available
2: Send stream was cut off; sending failed
3: Exhausted retries
4: No receive buffer available in Emac DMA
5: Emac DMA transfer aborted
6: Queue overflow
7: Unexpected frame received
ZInfo3: Number of errors, which occurred
0xEAB0 Link mode not valid
OBNo: Current PLC mode
ZInfo1: Diagnostics address master / controller
Zinfo2: Current LinkMode
0x01: 10Mbit full-duplex
0x02: 100Mbit half-duplex
0x03: 100Mbit full-duplex
0x05: 10Mbit half-duplex
0xFF: Link mode not defined
0xEB03 SLIO error on IO mapping
0xEB10 SLIO error: Bus error
ZInfo1: Type of error
0x82: ErrorAlarm
0xEB20 SLIO error: Interrupt information undefined
0xEB21 SLIO error on accessing the configuration data
VIPA System 300S Deployment CPU 315-4PN33
VIPA specific diagnostic entries
HB140 | CPU | 315-4PN33 | GB | 14-43 75