Event-ID Description
0xE01B Error - Maximum number of plug-in modules exceeded
0xE020 Error - Interrupt information is not defined
0xE030 Error of the standard bus
0xE033 Internal error - Please contact the VIPA Hotline!
0xE0B0 SPEED7 is not stoppable
(Probably undefined BCD value at timer)
0xE0C0 Not enough space in work memory for storing code block (block size
exceeded)
0xE0CB Error at SSL access
ZInfo1: 4=SSL wrong, 5=SubSSL wrong, 6=Index wrong
ZInfo2: SSL-ID
ZInfo3: Index
0xE0CC Communication error MPI / Serial
ZInfo1: Code
1: Wrong priority
2: Buffer overflow
3: Frame format error
4: Wrong SSL request (SSL-ID not valid)
5: Wrong SSL request (SSL-SubID not valid)
6: Wrong SSL request (SSL-Index not valid)
7: Wrong value
8: Wrong RetVal
9: Wrong SAP
10: Wrong connection type
11: Wrong sequence number
12: Faulty block number in the telegram
13: Faulty block type in the telegram
14: Inactive function
15: Wrong size in the telegram
20: Error writing to memory card
90: Faulty buffer size
98: Unknown error
99: Internal error
0xE0CD Error at DP-V1 job management
0xE0CE Error: Timeout at sending of the i-slave diagnostics
0xE0CF Timeout at loading of a new HW configuration (timeout: 39 seconds)
0xE100 Memory card access error
VIPA System 300S Deployment CPU 315-4PN33
VIPA specific diagnostic entries
HB140 | CPU | 315-4PN33 | GB | 14-43 67