315-4PN33

CAUTION!
When installing a new firmware you have to be extremely
careful. Under certain circumstances you may destroy the
CPU, for example if the voltage supply is interrupted
during transfer or if the firmware file is defective. In this
case, please call the VIPA-Hotline!
Please regard that the version of the update firmware has
to be different from the existing firmware otherwise no
update is executed.
The CPU has an integrated website that monitors information about
firmware version of the SPEED7 components. The Ethernet PG/OP
channel provides the access to this web site. The CPU has an inte-
grated website that monitors information about firmware version of
the SPEED7 components. The Ethernet PG/OP channel provides the
access to this web site. ‘PLC è Assign Ethernet Address’. After that
you may access the PG/OP channel with a web browser via the IP
address of the project engineering.
Ä
Chapter 5.10 ‘Access to the
internal Web page’ on page 52
n Go to www.vipa.com
n Click on ‘Service è Download è Firmware’.
n Navigate via ‘System 300S è CPU’ to your CPU and download
the zip file to your PC.
n Extract the zip file and copy the extracted pkg files to your MMC.
CAUTION!
With a firmware update an overall reset is automatically
executed. If your program is only available in the load
memory of the CPU it is deleted! Save your program
before executing a firmware update! After the firmware
update you should execute a "Set back to factory set-
tings".
Ä
Chapter 5.14 ‘Reset to factory setting’
on page 60
1. Switch the operating mode switch of your CPU in position
STOP. Turn off the voltage supply. Plug the MMC with the firm-
ware files into the CPU. Please take care of the correct plug-in
direction of the MMC. Turn on the voltage supply.
2. After a short boot-up time, the alternate blinking of the LEDs SF
and FC shows that at least a more current firmware file was
found on the MMC.
3. You start the transfer of the firmware as soon as you tip the
operating mode switch downwards to MRES within 10s.
4. During the update process, the LEDs SF and FC are alternately
blinking and MC LED is on. This may last several minutes.
5. The update is successful finished when the LEDs PW, ST, SF,
FC and MC are on. If they are blinking fast, an error occurred.
Display the Firmware
version of the SPEED7
system via Web Site
Load firmware and
transfer it to MMC
Transfer firmware from
MMC into CPU
VIPA System 300S Deployment CPU 315-4PN33
Firmware update
HB140 | CPU | 315-4PN33 | GB | 14-43 59