® The MC LED is on. When the reload has been completed the LED
expires. The operating mode of the CPU will be STOP respectively
RUN, depending on the position of the operating mode switch.
The Reset to factory setting deletes completely the internal RAM of
the CPU and resets this to delivery state. Please regard that the MPI
address is also set back to default 2!
Ä
Chapter 5.14 ‘Reset to factory
setting’ on page 60
5.13 Firmware update
n There is the opportunity to execute a firmware update for the CPU
and its components via MMC. For this an accordingly prepared
MMC must be in the CPU during the startup.
n So a firmware files can be recognized and assigned with startup,
a pkg file name is reserved for each updateable component an
hardware release, which begins with "px" and differs in a number
with six digits. The pkg file name of every updateable component
may be found at a label right down the front flap of the module.
n After PowerON and CPU STOP the CPU checks if there is a *.pkg
file on the MMC. If this firmware version is different to the existing
firmware version, this is indicated by blinking of the LEDs and the
firmware may be installed by an update request.
The latest firmware versions are to be found in the service area at
www.vipa.com. For example the following files are necessary for the
firmware update of the CPU 315-4PN33 and its components with
hardware release 1:
n 315-4PN33, Hardware release 1: Px000175.pkg
n PROFINET IO controller: Px000180.pkg
Reset to factory setting
Overview
Latest firmware at
www.vipa.com
VIPA System 300SDeployment CPU 315-4PN33
Firmware update