The structure of a MPI net is electrically identical with the structure of
a PROFIBUS net. This means the same rules are valid and you use
the same components for the build-up. The single participants are
connected with each other via bus interface plugs and PROFIBUS
cables. Please consider with the CP 315-4PN33 that the total exten-
sion of the MPI net does not exceed 50m. Per default the MPI net
runs with 187.5kbaud. VIPA CPUs are delivered with MPI address 2.
The MPI programming cables are available at VIPA in different var-
iants. The cables provide a RS232 res. USB plug for the PC and a
bus enabled RS485 plug for the CPU. Due to the RS485 connection
you may plug the MPI programming cables directly to an already
plugged plug on the RS485 jack. Every bus participant identifies itself
at the bus with an unique address, in the course of the address 0 is
reserved for programming devices.
A cable has to be terminated with its surge impedance. For this you
switch on the terminating resistor at the first and the last participant of
a network or a segment. Please make sure that the participants with
the activated terminating resistors are always power supplied. Other-
wise it may cause interferences on the bus.
1. Connect your PC to the MPI jack of your CPU via a MPI pro-
gramming cable.
2. Load your project in the SIMATIC Manager from Siemens.
3.
Choose in the menu ‘Options è Set PG/PC interface’.
4. Select in the according list the "PC Adapter (MPI)"; if appropriate
you have to add it first, then click on [Properties].
5. Set in the register MPI the transfer parameters of your MPI net
and type a valid address.
6. Switch to the register Local connection.
7. Set the COM port of the PCs and the transfer rate 38400Baud
for the MPI programming cable from VIPA.
8.
Via ‘PLC è Load to module
via MPI to the CPU and save it on
a MMC via ‘PLC è Copy RAM to ROM’ if one is plugged.
5.9.2 Transfer via Ethernet
For transfer via Ethernet the CPU has the following interface:
n X5: Ethernet PG/OP channel
Net structure
MPI programming cable
Terminating resistor
Approach transfer via
MPI interface
VIPA System 300SDeployment CPU 315-4PN33
Project transfer > Transfer via Ethernet
HB140 | CPU | 315-4PN33 | GB | 14-43 50