315-4PN33

1.
Perform a hardware configuration for the CPU.
Ä
Chapter 5.4
‘Hardware configuration - CPU’ on page 40
2. Configure always as last module a Siemens DP master CP
342-5 (342-5DA02 V5.0). Connect and parametrize it at opera-
tion mode "DP-Master".
3. Connect the slave system "VIPA_SPEEDbus". After installing
the SPEEDBUS.GSD this may be found in the hardware catalog
at Profibus-DP / Additional field devices / I/O / VIPA /
VIPA_SPEEDBUS.
4. For the slave system set the PROFIBUS address 100.
5. Configure at slot 0 the VIPA CPU 315-4PN33 of the hardware
catalog from VIPA_SPEEDbus.
6. By double clicking the placed CPU 315-4PN33 the properties
dialog of the CPU may be opened.
5.8.2
VIPA specific parameters
The following parameters may be accessed by means of the proper-
ties dialog of the VIPA-CPU.
5.8.2.1 Number remanence flag
Here the number of flag bytes may be set. With 0 the value Retentive
memory > Number of memory bytes starting with MB0 set at the
parameters of the Siemens CPU is used. Otherwise the adjusted
value (1 ... 8192) is used. Default: 0
5.8.2.2 Priority of OB 28 and OB 29
The priority fixes the order of interrupts of the corresponding interrupt
OB. Here the following priorities are supported: 0 (Interrupt-OB is
deactivated), 2, 3, 4, 9, 12, 16, 17, 24. Default: 24
5.9 Project transfer
There are the following possibilities for project transfer into the CPU:
n Transfer via MPI
n Transfer via Ethernet
n Transfer via MMC
5.9.1 Transfer via MPI
For transfer via MPI there is the following interface:
n X2: MPI interface
Overview
VIPA System 300S Deployment CPU 315-4PN33
Project transfer > Transfer via MPI
HB140 | CPU | 315-4PN33 | GB | 14-43 49