315-4PN33
n Number of S7 Counters from C0: Enter the number of retentive S7
counter from C0 onwards.
n Areas: This parameter is not supported.
n Priority: Here the priorities are displayed, according to which the
hardware interrupt OBs are processed (hardware interrupt, time-
delay interrupt, async. error interrupts).
n Priority: Here the priorities may be specified according to which
the time-of-day interrupt is processed. With priority "0" the corre-
sponding OB is deactivated.
n Active: Activate the check box of the time-of-day interrupt OBs if
these are to be automatically started on complete restart.
n Execution: Select how often the interrupts are to be triggered.
Intervals ranging from every minute to yearly are available. The
intervals apply to the settings made for start date and time.
n Start date/time: Enter date and time of the first execution of the
time-of-day interrupt.
n Process image partition: This parameter is not supported.
n Priority: Here the priorities may be specified according to which
the corresponding cyclic interrupt is processed. With priority "0"
the corresponding interrupt is deactivated.
n Execution: Enter the time intervals in ms, in which the watchdog
interrupt OBs should be processed. The start time for the clock is
when the operating mode switch is moved from STOP to RUN.
n Phase offset: Enter the delay time in ms for current execution for
the watch dog interrupt. This should be performed if several
watchdog interrupts are enabled. Phase offset allows to distribute
processing time for watchdog interrupts across the cycle.
n Process image partition: This parameter is not supported.
n Report cause of STOP: Activate this parameter, if the CPU should
report the cause of STOP to PG respectively OP on transition to
STOP.
n Number of messages in the diagnostics buffer: Here the number
of diagnostics are displayed, which may be stored in the diagnos-
tics buffer (circular buffer).
n Synchronization type: Here you specify whether clock should syn-
chronize other clocks or not.
–
as slave: The clock is synchronized by another clock.
– as master: The clock synchronizes other clocks as master.
– none: There is no synchronization
n Time interval: Time intervals within which the synchronization is to
be carried out.
n Correction factor: Lose or gain in the clock time may be compen-
sated within a 24 hour period by means of the correction factor in
ms. If the clock is 1s slow after 24 hours, you have to specify a
correction factor of "+1000" ms.
Interrupts
Time-of-day interrupts
Cyclic interrupts
Diagnostics/Clock
VIPA System 300SDeployment CPU 315-4PN33
Setting standard CPU parameters > Parameters CPU
HB140 | CPU | 315-4PN33 | GB | 14-43 46