315-4PN33
For project engineering a thorough knowledge of the Siemens
SIMATIC Manager and the Siemens hardware configurator is
required.
Please consider that this SPEED7-CPU has 4 ACCUs.
After an arithmetic operation (+I, -I, *I, /I, +D, -D, *D, /D,
MOD, +R, -R, *R, /R) the content of ACCU 3 and ACCU 4
is loaded into ACCU 3 and 2. This may cause conflicts in
applications that presume an unmodified ACCU 2.
For more information may be found in the manual "VIPA
Operation list SPEED7" at "Differences between SPEED7
and 300V programming".
To be compatible with the Siemens SIMATIC Manager the following
steps should be executed:
1. Start the Siemens hardware configurator with a new project.
2. Insert a profile rail from the hardware catalog.
3. Place at ‘Slot’ -Number 2 the CPU 315-2 PN/DP (315-2EH13
V2.6).
4. The PROFINET IO controller is to be configured via the sub
module ‘X2 PN-IO’ .
5.5
Hardware configuration - I/O modules
After the hardware configuration place the System 300 modules in the
plugged sequence starting with slot 4.
For parametrization double-click during the project engineering at the
slot overview on the module you want to parameterize. In the
appearing dialog window you may set the wanted parameters. By
using the SFCs 55, 56 and 57 you may alter and transfer parameters
for wanted modules during runtime. For this you have to store the
module specific parameters in so called "record sets". More detailed
information about the structure of the record sets is to find in the
according module description.
Proceeding
Hardware configuration
of the modules
Parametrization
VIPA System 300S Deployment CPU 315-4PN33
Hardware configuration - I/O modules
HB140 | CPU | 315-4PN33 | GB | 14-43 41