315-4PN33

RN
(RUN)
ST
(STOP)
SF
(SFAIL)
FC
(FRCE)
MC
(MMC)
Meaning
BB BB The alternate blinking indicates that there is new
firmware on the memory card.
BB BB The alternate blinking indicates that a firmware
update is executed.
Firmware update finished without error.
BB* BB* BB* BB* * Blinking with 10Hz: Error during Firmware
update.
on: ● | off: ○ | blinking (2Hz): BB | not relevant: X
LEDs Ethernet PG/OP channel L/A, S
The green L/A-LED (Link/Activity) indicates the physical connection of the Ethernet PG/OP
channel to Ethernet. Irregular flashing of the L/A-LED indicates communication of the Ethernet
PG/OP channel via Ethernet.
If the green S-LED (Speed) is on, the Ethernet PG/OP has a communication speed of 100MBit/s
otherwise 10MBit/s.
MT
(Mainte-
nance)
BF
(Bus error)
Meaning
yellow red
X
n Bus error, no connection to sub net/switch
n wrong transfer rate
n Full-duplex-transmission is not activated
X BB
n Failure of a connected IO device
n At least one IO device is not access-able
n Faulty configuration
X Maintenance event is pending.
BB * BB * * The alternate blinking with 4Hz indicates that a firmware update of
the PROFINET IO controller is executed.
Firmware update of the PROFINET IO controller is finished without
error.
BB X With a suited configuration tool you can cause the LED to blink by
means of the function ‘member blink test’ . This can be usefull for e.g.
identification of the module.
on: ● | off: ○ | blinking (2Hz): BB | not relevant: X
LEDs L/A, S
The green L/A-LED (Link/Activity) indicates the physical connection of the PROFINET IO con-
troller to Ethernet. Irregular flashing of the L/A-LED indicates communication of the PROFINET
IO controller via Ethernet.
If the green S-LED (Speed) is on, the PROFINET IO controller has a communication speed of
100MBit/s otherwise with 10MBit/s.
LEDs PROFINET IO
controller X8
VIPA System 300SHardware description
Structure > LEDs
HB140 | CPU | 315-4PN33 | GB | 14-43 30