315-4PN33

9.5 TIA Portal - Hardware configuration - PG/OP via PROFINET
The CPU has a twisted pair interface integrated for PROFINET This
interface allows you to program and remote control your CPU.
n The PROFINET interface also gives you access to the internal
web page that contains information about firmware version, con-
nected I/O devices, current cycle times etc.
n At the first commissioning respectively after a factory reset the
PROFINET interface has no IP address.
n For online access to the CPU via the PROFINET interface, valid
IP address parameters have to be assigned to this. This is called
"initialization".
n This can be done with the Siemens TIA Portal.
1. Install your System 300S with your CPU.
2. Wire the system by connecting cables for voltage supply and
signals.
3. Connect the Ethernet jack PROFINET to Ethernet.
4. Switch on the power supply.
ð
After a short boot time the CP is ready for communication.
He possibly has no IP address data and requires an initiali-
zation.
The initialization via the Online functions takes place with the fol-
lowing proceeding:
Determine the current Ethernet (MAC) address of your PRO-
FINET interface. This can be found as 2. address under the front
flap of the CPU on a sticker on the left side.
You get valid IP address parameters from your system administrator.
The assignment of the IP address data happens online in the Sie-
mens TIA Portal with the following proceeding:
1. Start the Siemens TIA Portal.
2. Switch to the ‘Project view’ .
3. Click in the ‘Project tree’ at ‘Online access’ and choose here by
a doubleclick your network card, which is connected to the PRO-
FINET interface.
4. To get the stations and their MAC address, use the ‘Accessible
device’ . The MAC address can be found at the 2. label beneath
the front flap of the CPU.
5. Choose from the list the module with the known MAC address
(PROFINET CP [MAC address]) and open with "Online & Diag-
nostics" the diagnostics dialog in the Project area.
6. Navigate to Functions > Assign IP address. Type in the IP con-
figuration like IP address, subnet mask and gateway.
Overview
Assembly and commis-
sioning
"Initialization" via
Online functions
Assign IP address
parameters
VIPA System 300S Configuration with TIA Portal
TIA Portal - Hardware configuration - PG/OP via PROFINET
HB140 | CPU | 315-4PN33 | GB | 14-43 153