315-4PN33

n For the communication between IO controller and IO device the
ways for the communication are to be defined before. For the
clear specification of the communication ways, these are estab-
lished during the start-up by the IO controller, based on the project
data. Here the configuration takes place by a hardware configura-
tion.
n As soon as the project data were transmitted, the IO controller
switches to system start-up.
n In this state the IO controller may be accessed and its CPU may
be configured via Ethernet by the IO controller by means of the IP
address.
n The PROFINET IO controller is configured by a hardware configu-
ration. After the transmission of the project into the IO controller
with connected IO devices, the IO controller has the whole infor-
mation for the addressing of and the data exchange with the IO
devices.
n During the system start-up of the IO controller the IO devices are
supplied with their configured IP address by means of the DCP
protocol. After PowerON due to the project data the system start-
up of the IO controller is initialized and it runs off independently.
During the system start-up the IO controller establishes a clear
communication relation (CR) and an application relation (AR) to
an IO-Device. Here the cyclic IO data, the acyclic R/W services
and the expected modules/sub modules are specified.
n If the IO controller has received valid project engineering data, a
system start-up with the IO devices is initialized and this is indi-
cated by flashing BF LED. The BF LED is on with configured
PROFINET IO device and bus cable is missing.
n If at least one IO device is not in cyclic data exchange during
start-up, the BF LED blinks.
n If all IO devices are in cyclic data exchange, the BF LED gets off.
This state does not depend on the state of the operating mode
switch of the CPU. After a successful system start-up the system
is ready for communication.
After PowerON respectively a receipt of a new hardware configuration
the configuration data are automatically transferred to the IO con-
troller. Dependent on the CPU state the following behaviour is shown
by the IO controller:
n Behaviour at CPU STOP
In the STOP state of the CPU an output telegram is further
cyclically sent but this is designated as "not valid" and the
output data are set to 0.
The IO controller further receives the input data of the IO
devices and transfers them cyclically to the input area of the
CPU.
n Behaviour at CPU RUN
The IO controller cyclically reads the output data from the CPU
and transfers these as telegram to the connected IO devices.
The IO controller receives the input data of the IO devices and
transfers them cyclically to the input area of the CPU.
Online with bus param-
eters without project
IO device configuration
CPU state influences
the IO process data
VIPA System 300SDeployment Ethernet communication - PROFINET
Commissioning and start-up behaviour
HB140 | CPU | 315-4PN33 | GB | 14-43 142