315-4PN33
2. Here you have the following parameters:
n Port interconnection
–
Local port: Name of the local port
– Medium: Specifying the line type (copper, fibre optic
cable). Currently, this parameter is not evaluated.
– Cable name Specifying a cable name
n Partners
– Partner port: Name of the port to which the selected port
is interconnected.
– Alternating partner ports: By specifying at ‘Partner port’
"Any partner", you can configure alternating partner ports
for the I/O devices. Currently, this parameter is not evalu-
ated.
n Cable data
– Cable length: Depending on the port medium you can set
in the select list the cable length, if the medium between
two stations does not change. Here the signal delay time
is automatically calculated. Currently, this parameter is
not evaluated.
– Signal delay time: If the medium between two stations
changes, a signal delay time can be defined here. Cur-
rently, this parameter is not evaluated.
3. Close the properties dialog with [OK] again.
8.11
Device replacement without exchangeable medium/PG
Please consider that for this function the Siemens CPU
315-2 PN/DP (6ES7 315-2EH14-0AB0, V3.2) is to be used
of the hardware catalog. For this the Siemens SIMATIC
Manager V 5.5, SP2 and up is to be used.
IO devices, which support the PROFINET function Device replace-
ment without exchangeable medium/PG get their device name from
the controller with the exchange. These can be replaced without
installing an "exchangeable medium" (memory card) with the stored
device name respectively without assigning a device name by a PG.
To assign the device name the IO controller uses the configured Top-
ology and the "neighbourhood relationship", which is determined by
the IO devices.
Thus the Device replacement without exchangeable medium/PG is
possible, the following requirements must be met:
n The Topology of your PROFINET IO system with the corre-
sponding IO devices must be configured.
n The IO controller and the respective adjacent to the unit to be
replaced IO device must support the functionality Device replace-
ment without exchangeable medium/PG.
n In the IO controller in the ‘Properties’ the option Support device
replacement without exchangeable medium must be enabled.
n The replaced device must be reset to delivery state, before.
Overview
VIPA System 300SDeployment Ethernet communication - PROFINET
Device replacement without exchangeable medium/PG
HB140 | CPU | 315-4PN33 | GB | 14-43 140