315-4PN33
Please consider that this SPEED7-CPU has 4 ACCUs.
After an arithmetic operation (+I, -I, *I, /I, +D, -D, *D, /D,
MOD, +R, -R, *R, /R) the content of ACCU 3 and ACCU 4
is loaded into ACCU 3 and 2. This may cause conflicts in
applications that presume an unmodified ACCU 2.
For more information may be found in the manual "VIPA
Operation list SPEED7" at "Differences between SPEED7
and 300V programming".
To be compatible with the Siemens SIMATIC Manager the following
steps should be executed:
1. Start the Siemens hardware configurator with a new project.
2. Insert a profile rail from the hardware catalog.
3. Place at ‘Slot’ -Number 2 the CPU 315-2 PN/DP (315-2EH13
V2.6).
4. The PROFINET IO controller is to be configured via the sub
module ‘X2 PN-IO’ .
8.7
Parameters - PROFINET IO controller
8.7.1 Precondition
To parametrize the PROFINET IO controller of the CPU, the following
conditions must be fulfilled:
n The PROFINET IO controller is online reachable, this means an
initialization was established.
n The hardware configuration described before was established and
the PROFINET IO controller is networked.
Open the properties dialog of the PROFINET IO controller by a
double-click at PN-IO.
The PROFINET interface of the PROFINET IO controller is parame-
trized with PN-IO, the port with Port 1. In the following these parame-
ters for PN-IO and Port 1 are described.
Proceeding
Proceeding
VIPA System 300S Deployment Ethernet communication - PROFINET
Parameters - PROFINET IO controller > Precondition
HB140 | CPU | 315-4PN33 | GB | 14-43 135