8.4 Fast introduction
Range of functions
Please regard that the PROFINET IO controller supports
only the PROFINET functions, which are described in this
manual, even if the Siemens CPU, which is used for con-
figuration, offers further functions! To use some described
PROFINET functions, it is necessary to deploy another
Siemens CPU for configuration. Here, however, is pointed
to explicitly.
At the first commissioning respectively after an overall reset with
PowerON again of the CPU, the Ethernet PG/OP channel and the
PROFINET IO controller have no IP address. These are only reach-
able by its MAC address. IP address parameters may be assigned to
the corresponding component by means of the MAC addresses,
which may be found on labels beneath the front flap with the
sequence 1. address PG/OP channel and beneath address of the
PROFINET IO controller. The assignment takes place directly via the
hardware configuration of the Siemens SIMATIC manager.
The configuration of the PROFINET IO controller for PROFINET com-
munication should be done by the following procedure:
1. Commissioning and Initialization (assignment IP address data)
2. Hardware configuration - CPU
3. Configuration PROFINET IO controller
4. Configuration PROFINET IO device
5. Transfer of the entire project to the CPU
To be compatible with the Siemens SIMATIC Manager the
CPU 315-4PN33 from VIPA is to be configured as
CPU 315-2 PN/DP (315-2EH13-0AB00 V2.6)!
The Ethernet PG/OP channel of the CPU 315-4PN33 is to
be configured as 1. module as CP 343-1 (343-1EX11)
from Siemens after the really plugged modules at the
standard bus.
8.5 Commissioning and Initialization
1. Install your System 300S with your CPU.
2. Wire the system by connecting cables for voltage supply and
signals
3. Connect your PROFINET IO controller with Ethernet.
4. Switch on the power supply.
ð
After a short boot time, the CP is in idle.
At the first commissioning respectively after an overall reset
of the CPU, the PROFINET IO controller and the Ethernet
PG/OP channel have no IP address.
Overview
Steps of configuration
Assembly and commis-
sioning
VIPA System 300S Deployment Ethernet communication - PROFINET
Commissioning and Initialization
HB140 | CPU | 315-4PN33 | GB | 14-43 133