315-4PN33
n Configure connections
–
Siemens S7 connections
(Configuration via Siemens NetPro, communication via VIPA
handling blocks)
– Open communication
(Configuration and communication happens by standard han-
dling blocks)
n Transfer of the complete project to CPU
To be compatible to the Siemens SIMATIC Manager, the
CPU 315-4PN33 from VIPA is to be configured as CPU
315-2 PN/DP (6ES7 315-2EH13-0AB0 V2.6)!
The PROFINET IO controller is to be configured via the
CPU sub module X2 (PN-IO).
The Ethernet PG/OP channel of the CPU 315-4PN33 is
always to be configured as 1. module after the really
plugged modules at the standard bus as CP 343-1
(343-1EX11) from Siemens.
7.7 Commissioning and initialization
1. Install your System 300S with your CPU.
2. Wire the system by connecting cables for voltage supply and
signals
3. Connect your PROFINET IO controller with Ethernet.
4. Switch on the power supply.
ð
After a short boot time, the CP is in idle. At the first commis-
sioning res. after an overall reset of the CPU, the PROFINET
IO controller and the Ethernet PG/OP channel have no IP
address.
You get valid IP address parameters from your system administrator.
The assignment of the IP address data happens online in the Sie-
mens SIMATIC Manager starting with version V 5.3 & SP3 with the
following proceeding:
1. Start the Siemens SIMATIC Manager and set via ‘Options
è Set PG/PC interface
’the access path to ‘TCP/IP -> Network
card ....’ .
2.
Open with ‘PLC è Edit Ethernet Node n
’ the dialog window with
the same name.
3. To get the stations and their MAC address, use the [Browse]
button or type in the MAC Address. The Mac address may be
found at the 2. label beneath the front flap of the CPU.
4. Choose if necessary the known MAC address of the list of found
stations. To check this with [Blink] you may cause the MT LED
to blink.
Assembly and commis-
sioning
Assign IP address
parameters
VIPA System 300SDeployment Ethernet communication - productive
Commissioning and initialization
HB140 | CPU | 315-4PN33 | GB | 14-43 114