PowerEdge R710 Technical Guide 50
Depending on the depth of the rack used, it may be necessary to remove the server’s bezel in order to close
the door of the rack. A minimum of 58 mm is needed between the back surface of the door panel and the front
face of the EIA flange for the front door to close with the 11G server bezel installed.
2U Threaded Rack Adapter Brackets Kit Figure 12.
The static rails support a wider variety of racks than the sliding rails but do not support serviceability in the
rack and are not compatible with the CMA.
R710 Static Rails Figure 13.
One key factor in selecting the proper rails is identifying the type of rack in which they will be installed. Both
the sliding rails and the static rails support tool-less mounting in 19”-wide, EIA-310-E compliant 4-post racks,
but only the static rails, as the more generic or universal solution, support mounting in threaded hole and 2-
post (Telco) racks.